Remote-sealed
Differential Pressure Transmitters
AT9000 Advanced Transmitter
Remote-sealed Differential Pressure Transmitters (GTX**R series) are used to
measure differential pressure (flow rate, fluid level, etc.) of
high-temperature or highly corrosive, condensable fluids. We offer an extensive
lineup including small bore flange models starting at 40 mm and models for high
temperature (including high temperature high vacuum) applications.
Remote-sealed
Differential Pressure Transmitters
MODEL
|
GTX35R
|
GTX40R
|
MEASUREMENT SPAN
|
2.5 to 100 kPa
|
35 to 700 kPa
|
SETTING RANGE
|
-100 to 100 kPa
|
-100 to 700 kPa
|
REFERENCE ACCURACY
(VARIES BY
MATERIAL AND MEASUREMENT SPAN)
|
±0.2%
|
±0.2%
|
FILL FLUID
|
Silicone oil (for
the following models: general purpose, high temperature, high temperature
vacuum, and high temperature high vacuum)
Fluorine oil (oxygen and chlorine models)
|
WATERPROOF AND DUST-PROOF CONSTRUCTION
|
IEC IP66/IP67
|
EXPLOSION-PROOF CONSTRUCTION
|
TIIS flameproof
(Exd IICT4)
KOSHA flameproof
FM explosion proof, intrinsic safe and Nonincendive
ATEX/NEPSI/IECEx flameproof, intrinsic safe and Type n
INMETRO flameproof
|
RANGE OF OPERATING TEMPERATURES FOR LIQUID PART
(VARIES WITH
PRESSURE)
|
Silicone oil: -40
to 280 °C (varies with fill fluid)
Fluorine oil: -10 to 120 °C
|
RANGE OF OPERATING PRESSURES FOR LIQUID PART
(VARIES WITH
TEMPERATURE)
|
Silicone oil for
general purpose and high temperature models: from 2 kPa abs
High temperature vacuum and high temperature high vacuum models: from 0.13
kPa abs
Fluorine oil: from 53 kPa abs
|
WETTED MATERIAL
|
SUS316 (diaphragm
SUS316L), Hastelloy C, Tantalum
|
POWER
|
17.9 to 42V DC
|
OUTPUT SIGNAL
|
4 to 20 mA DC
(SFN communication)
4 to 20 mA DC (HART® communication)
|
FLANGE BORE
|
Flush models: 80
mm, 50 mm, 40 mm. Protruding models: 100 mm, 80 mm, 50 mm
|
SAFETY CERTIFICATION
|
Safety Integrity
Level (SIL) 2 certification
|
Excellent long-term stability
Zero drift: long-term
stability of only ±0.1 % drift over 10 years
Fast response
Response speed: 100
ms or faster; can be used in applications that require fast response.
Wide measuring range (rangeability)
This single model
offers a wide measurement range, which is very useful for both expanding the
scope of measurement and reducing the equipment needed. Rangeability 1:400
Very user-friendly
Zero/span adjustment
can be done without opening the cover.
Multiple functions
Historical data
(e.g., on excessive pressures or abnormal temperatures) can be retrieved by a
communicator.