47LYV DC INPUT DIGITAL PANEL METER (4 1/2 digit, process meter, LED display type)
Functions & Features • 4 ½ digit DC input digital panel meter • 1/8 DIN size • Moving average function to suppress the display flickering • Scaling, forced zero, low-end cutout • Max. and Min. value display • Safety terminal cover tethered to the device with a strap • IP66 front panel • Separable terminal block
MODEL: 47LYV-[1][2]-[3][4]
ORDERING INFORMATION • Code number: 47LYV-[1][2]-[3][4] Specify a code from below for each [1] through [4]. (e.g. 47LYV-AR-M2/Q) • Specify the specification for option code /Q (e.g. /C01/S01/SET)
[1] INPUT Current A: 4 – 20 mA DC (Input resistance approx. 10 Ω) D: 0 – 20 mA DC (Input resistance approx. 10 Ω) Voltage 5: 0 – 5 V DC (Input resistance 1 MΩ min.) 6: 1 – 5 V DC (Input resistance 1 MΩ min.) 4W: -10 – +10 V DC (Input resistance 1 MΩ min.) 5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
[2] DISPLAY COLOR R: Red YR: Orange
[3] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[4] OPTIONS blank: none /Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) Moving parts and indicators are not coated. /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-9514)
GENERAL SPECIFICATIONS Construction: Panel flush mounting Degree of protection: IP66; applicable to the front of the panel meter mounted according to the specified panel cutout Connection: M3 separable screw terminal (torque 0.6 N·m) Screw terminal: Nickel-plated steel (standard) or stainless steel Housing material: Flame-resistant resin (gray) Isolation: Input to power Setting: (Front button) • Scaled range • Moving average • Others (Refer to the instruction manual for details) Read rate: 40 times/sec. (25 msec.) Averaging: None or moving average Lockout setting: Prohibiting certain operations; protecting settings
DISPLAY Display: 16 mm (.63) high, 4 ½ digits, 7-segment LED Display range: -19999 to 19999 Decimal point position: 10–1, 10–2, 10–3, 10–4 or none Zero indication: Higher-digit zeros are suppressed. Over-range indication: ‘-19999’ or ‘19999’ blinking for display values out of the display range. ‘S.ERR’ and ‘Min’ or ‘Max’ blinking when the input signal is out of the usable range. Function indicators: Zro, Spn, D/P, Tch, Fnc, Min, Max Display mode status and operation status, amber ON or blink Engineering unit indication: Sticker label attached DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min, cm/min, m/min, m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec, m3/min, m3/h, Nm3/h, N·m, N/m2, g, kg, kg/h, N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J, kJ, MJ, rpm, sec, min, min-1, pH, %, ppm, etc.
INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated Measurable range: -10 – +110 % ■ DC Voltage Measurable range: -10 – +110 %
INSTALLATION Power consumption •AC: Approx. 4 VA •DC: Approx. 2 W Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Panel flush mounting Weight: 250 g (0.55 lb)
PERFORMANCE Accuracy: ±0.1 % ±1 digit Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Input resolution: 16 bits Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to power to ground)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input to power: Reinforced insulation (300 V) RoHS Directive EN 50581 Protection against access to the terminal blocks: Finger protection (VDE 0660-514)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
MOUNTING REQUIREMENTS unit: mm
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM