M3SDY CURRENT LOOP SUPPLY
Functions & Features • Powers a two-wire transmitter and galvanically isolates its output signal • High-density mounting • Power indicator LED
MODEL: M3SDY–[1]–R[2]
ORDERING INFORMATION • Code number: M3SDY-[1]-R[2] Specify a code from below for each [1] and [2]. (e.g. M3SDY-A-R/Q) • Specify the specification for option code /Q (e.g. /C01)
INPUT Current 4 – 20 mA DC (Input resistance 249.5 Ω)
[1] OUTPUT Current A: 4 – 20 mA DC (Load resistance 550 Ω max.) Voltage 4: 0 – 10 V DC (Load resistance 10 kΩ min.) 5: 0 – 5 V DC (Load resistance 5000 Ω min.) 6: 1 – 5 V DC (Load resistance 5000 Ω min.)
POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS Other Options blank: none /Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
GENERAL SPECIFICATIONS Construction: Small-sized front terminal structure Connection: Euro type connector terminal Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm Housing material: Flame-resistant resin (gray) Isolation: Input to output to power Zero adjustment: -2 to +2 % (front) Span adjustment: 98 to 102 % (front) Power LED: Green light turns on when the power is supplied.
SUPPLY OUTPUT (across the terminals 3 – 4) Output voltage: 24 – 28 V DC with no load 18 V DC min. at 20 mA Current rating: ≤ 22 mA DC • Shortcircuit Protection Current limited: 45 mA max. Protected time duration: No limit
INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated
INSTALLATION Power consumption •DC: Approx. 1 W Operating temperature: -20 to +55°C (-4 to +131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: DIN rail Weight: 100 g (3.53 oz)
PERFORMANCE in percentage of span Accuracy: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 100 msec. (0 – 90 %) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Việt Nam Email: Sales@m-system.com.vn
|