M60SWVS SIGNAL TRANSMITTER (field-configurable, two isolated outputs)
Functions & Features • Converts DC input from a sensor into a standard process signal • Output range and response time selectable with DIP SW • Power connector for interconnecting modules and collectively supplying power • Spring clamp terminal connection for easy wiring • 6-mm wide ultra-slim design • Low profile allows mounting in a 120-mm deep panel • High-density mounting • Power indicator LED
MODEL: M60SWVS-R[1]
ORDERING INFORMATION • Code number: M60SWVS-R[1] Specify a code from below for [1]. (e.g. M60SWVS-R/Q) • Specify the specification for option code /Q (e.g. /C01) • Default at shipment Input range: 4 – 20 mA DC Output 1 range: 4 – 20 mA DC Output 2 range: 4 – 20 mA DC Response time: Standard response
INPUT – Field-selectable Current 4 – 20 mA DC (Input resistance 50 Ω) 0 – 20 mA DC (Input resistance 50 Ω) Voltage 0 – 10 V DC (Input resistance 200 kΩ min.) 2 – 10 V DC (Input resistance 200 kΩ min.) 0 – 5 V DC (Input resistance 100 kΩ min.) 1 – 5 V DC (Input resistance 100 kΩ min.)
OUTPUT 1 – Field-selectable Current 4 – 20 mA DC (Load resistance 300 Ω max.) 0 – 20 mA DC (Load resistance 300 Ω max.) Voltage 0 – 5 V DC (Load resistance 5000 Ω min.) 1 – 5 V DC (Load resistance 5000 Ω min.)
OUTPUT 2 – Field-selectable Current 4 – 20 mA DC (Load resistance 300 Ω max.) 0 – 20 mA DC (Load resistance 300 Ω max.) Voltage 0 – 5 V DC (Load resistance 5000 Ω min.) 1 – 5 V DC (Load resistance 5000 Ω min.)
POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS blank: none /Q: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating
GENERAL SPECIFICATIONS Connection Input and output: Spring clamp terminal Power input: Via the power connector or the spring clamp terminal Applicable wire size: 0.2 to 1.5 mm2, stripped length 8 mm Housing material: Flame-resistant resin (black) Isolation: Input to output 1 to output 2 to power Zero adjustment: -2 to +2 % (front) Span adjustment: 98 to 102 % (front) Adjustable individually for each output 1 and output 2. Power LED: Green LED turns on when the power is supplied.
INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated
INSTALLATION Power consumption: 0.7 W max. Power input: 3 A (Total current consumed by the interconnected signal conditioners must be 3 A or less.) Operating temperature: -20 to +55°C (-4 to +131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: DIN rail Weight: 65 g (2.3 oz)
PERFORMANCE in percentage of span Accuracy: ±0.1 % I/O setting accuracy: ±0.2 % Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) Response time (0 – 90 %): selectable with DIP SW Standard: ≤ 500 msec. Fast: ≤ 5 msec. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @1 minute (input to output 1 to output 2 to power to ground)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581
EXTERNAL VIEW Refer to the instruction manual for the setting procedure.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Việt Nam Email: Sales@m-system.com.vn
|