MDC6 DC POWER SUPPLY (maintenance forecast monitor function)
Functions & Features • Accepts 100 – 240 V AC and provides regulated 24 V DC output • Maintenance forecast monitor function
MODEL:MDC6–12024A–M2
ORDERING INFORMATION • Code number: MDC6-12024A-M2
CAPACITY 120: 120 W
OUTPUT VOLTAGE 24: 24 V DC
MONITOR A: Maintenance forecast monitor function
POWER INPUT AC Power M2: 100 – 240 V AC
GENERAL SPECIFICATIONS Construction: Front terminal access; terminal cover provided Connection: M4 screw terminals (torque 1.08 N·m) Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (beige); aluminum
SUPPLY OUTPUT Output voltage: 24 V DC -10/+15 %; adjustable on the front (ripple 2.0 %p-p max.) Load current: ≤ 5 A Overload protection: Voltage drop characteristics (105 %) Overload detecting: 105 % of the rated current
■ Alarm Output Transistor: NPN (sink) type; 30 V DC max., 50 mA DC max. Residual voltage at ON: ≤ 2 V Leakage current at OFF: ≤ 0.1 mA
INSTALLATION Power input AC: Operational voltage range 85 – 264 V AC 50/60 Hz Operating temperature: 0 to 50°C (32 to 122°F) Operating humidity: 25 to 85 % RH (non-condensing) Mounting: DIN rail Weight: 550 g (1.21 lb)
PERFORMANCE Temp. coefficient: ±0.05 %/°C (±0.03 %/°F) Load effect: ≤ 1.5 % Line voltage effect: ±0.5 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 3000 V AC @ 1 minute (output to power input) 2000 V AC @ 1 minute (power input to ground) 1000 V AC @ 1 minute (output to ground)
STANDARDS & APPROVALS EU conformity: EMC Directive EN 61204-3 (Class A) Low Voltage Directive EN 50178 EN 60950-1 RoHS Directive EN 50581 Approval: UL 508 (Class 2: per UL 1310) CAN/CSA C22.2 No.14 UL 60950-1 (Class 2) CAN/CSA C22.2 No.60950-1 VDE1060 VDE0805-1+A11
EXTERNAL VIEW
DIMENSIONS unit: mm (inch)
MOUNTING REQUIREMENTS unit: mm (inch)
CONNECTION DIAGRAM
M-System Co., Ltd.M-System Việt Nam Email: Sales@m-system.com.vn
|