·Some details are not shown. Please refer to specification sheets for all information.
FAMCL-01
Remote I/O FAM Series
CC-Link MASTER MODULE (Yokogawa Electric PLC use)
MODEL: FAMCL-01
ORDERING INFORMATION • Code number: FAMCL-01
RELATED PRODUCTS • Yokogawa Electric PLC: FA-M3V Recommended CPU module: F3SP71-4S, F3SP76-7S, F3SP22 • Configurator software (model: FAMCLCFG) Configurator software downloadable at M-System’s web site. In order to use FAMCLCFG, YOKOGAWA Electric Corporation 'WideField3' (R.3.02 or later) is required. FAMCL-01 and a PC are connected through the CPU unit of FA-M3V.
GENERAL SPECIFICATIONS Connection CC-Link: Separable tension clamp terminal Cable connector: TFMC1,5 / 5–STF–3,5 (Phoenix Contact) (included in the package) Applicable wire size: 0.2 − 1.5 mm2; stripped length 10 mm Recommended solderless terminal • AI0,25−10YE 0.25 mm2 (Phoenix Contact) • AI0,34−10TQ 0.34 mm2 (Phoenix Contact) • AI0,5−10WH 0.5 mm2 (Phoenix Contact) • AI0,75−10GY 0.75 mm2 (Phoenix Contact) • A1−10 1.0 mm2 (Phoenix Contact) • A1,5−10 1.5 mm2 (Phoenix Contact) Internal bus: Via the Installation Base InternalPower: Via the Installation Base Max. installable module: 2 Installable unit: Main unit and sub unit Isolation: CC-Link or FG to internal bus or internal power Status indicator LEDs: • RDY, RUN, LRUN, SD, RD: Green LED • ERR, LERR: Red LED
CC-Link COMMUNICATION CC-Link: Ver. 1.10/2.00 Master function: Master station (local station, standby master station not supported) Station address: 00 (Use with '00'. Works as '00' even set to other than '00'.) Supported slave station: Remote I/O station Remote device station (Ver. 1.10) Remote device station (Ver. 2.00) Intelligent device station, local station not supported Max. number of units connected: 64 (Remote I/O station) 42 (Remote device station) Max. number of link points: RX: 8192 (Data unit: bit) RY: 8192 (Data unit: bit) RWr: 2048 (Data unit: word) Rww: 2048 (Data unit: word) Protocol: CC-Link Ver. 1.10 conformed Network topology: Multi-drop Max. overall cable extension length: 100 m (10 Mbps), 160 m (5 Mbps), 400 m (2.5 Mbps), 900 m (625 kbps), 1200 m (156 kbps) Transmission media: CC-Link Ver. 1.10 compatible cable Operational station: Master station Operational mode: On-line mode Communication mode: Cyclic transmission Baud rate: 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps, set with rotary switch Slave station settings: With configurator software (model: FAMCLCFG)
INSTALLATION Current consumption: 600 mA @ 5V DC Operating temperature: 0 to 55°C (32 to 131°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base Module (model: F3BUxx-0N or F3BU05-0D) Weight: 150 g (0.33 lb)
PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (CC-Link or FG to internal bus or internal power)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581