ORDERING INFORMATION • Code number: R6N-DC4A[1] Specify a code from below for [1]. (e.g. R6N-DC4A/Q) • Specify the specification for option code /Q (e.g. /C01)
[1] OPTIONS blank: none /Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating
RELATED PRODUCTS • PC configurator software (model: R6CON) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R6N-BS) Output: M3 screw terminals (torque 0.5 N·m) Internal power: Via the Installation Base (model: R6N-BS) Recommended solderless terminal: Max. 5.8 mm (0.23”) wide; Ones with insulation sleeve do not fit. Applicable wire size: 0.2 – 2.5 mm2 Housing material: Flame-resistant resin (black) Isolation: Output to internal bus or internal power Module address: Selectable with DIP and rotary switches on the side Output at the loss of communication: Selectable with the side DIP SW Configuration mode: With DIP switches on the side panel Power indicator: Green LED; Refer to the istruction manual for details. Status indicator: Bi-color (red/green) LED; Refer to the instruction manual for details. Discrete output status indicators: Red LED; Refer to the instruction manual for details.
OUTPUT Common: Negative common (NPN) per 4 points Number of I/O: Output, 4 points Maximum outputs applicable at once: No limit (at 24 V DC) Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION Current consumption: 20 mA Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R6N-BS) Weight: 60 g (2.1 oz)
PERFORMANCE Data allocation: 1 Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (output to internal bus or internal power to ground)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)