·Some details are not shown. Please refer to specification sheets for all information.
R1M-J3/MSR
PC Recorders R1M Series
PC RECORDER (RTD or potentiometer input, 8 points)
Functions & Features • Industrial recorder on PC • 8-point RTD or potentiometer inputs • Easy system expansion via Modbus RTU • Recorded data exportable to spreadsheet applications
MODEL: R1M-J3T-[1][2]
ORDERING INFORMATION • Code number: R1M-J3T-[1][2] Specify a code from below for each [1] and [2]. (e.g. R1M-J3T-M2/MSR/Q) • Specify the specification for option code /Q (e.g. /C01)
FIELD TERMINAL TYPE T:M3 screw terminals
[1] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS (multiple selections) PC Recorder Software Package (must be specified) /MSR: With Other Options blank: none /Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
PACKAGE INCLUDES... • PC Recorder Software CD • 9-pin D-sub connector, straight type (1 m or 3.3 ft)
GENERAL SPECIFICATIONS Connection Power input, transmission: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 – 12), stripped length 7 mm) RS-232-C: 9-pin D-sub connector (male) (Lock screw No. 4-40 UNC) Input: M3 screw terminals (torque: 0.6N·m) Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Isolation: Input to RS-232-C or RS-485 to power Node address setting: Rotary switch; 1 – F (15 nodes) RUN indicator LED: Green light blinks in normal conditions.
INPUT SPECIFICATIONS Input: RTD or potentiometer input, 8 points Maximum leadwire resistance: 20 Ω per wire (3-wire) Sensing current: ≤ 1 mA RTDs: JPt 100 (JIS ’89), Pt 100 (JIS ’89), Pt 100 (JIS ’97, IEC), Pt 50 Ω (JIS ’81), Ni 508.4 Ω, Pt 1000 Potentiometers: 0 – 100 Ω, 0 – 500 Ω, 0 – 1 kΩ, 0 – 10 kΩ Sampling rate: 100 msec./8 points • Trigger input: Dry contact; ON detected at ≤ 1.5 V Sensing: Approx. 5 V DC @ 1 mA
INSTALLATION Power consumption •AC: Approx. 10 VA •DC: Approx. 7 W Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 400 g (0.88 lb)
PERFORMANCE (% of measuring range) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to RS-232-C or RS-485 to power to FG)
STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input or RS-232-C/RS-485 to power: Reinforced insulation (300 V) Input to RS-232-C/RS-485: Basic insulation (300 V) RoHS Directive EN 50581
PC RECORDER SOFTWARE PC Recorder Software Package (model: MSRPAC-2010) is included with purchases of this model. Refer to the MSRPAC-2010 data sheet for the contents of the package and the requirements for the PC to be prepared by the user.
EXTERNAL VIEW
MODBUS WIRING CONNECTION
CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)