·Some details are not shown. Please refer to specification sheets for all information.
R5-NF1
Remote I/O R5 Series
T-Link INTERFACE MODULE (Fuji Electric T-Link use)
MODEL: R5-NF1[1]
ORDERING INFORMATION • Code number: R5-NF1[1] Specify a code from below for [1]. (e.g. R5-NF1/Q) • Specify the specification for option code /Q (e.g. /C01)
[1] OPTIONS blank: none /Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
GENERAL SPECIFICATIONS Connection T-Link: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG 24 to 12), stripped length 7 mm) Internal bus: Via the Installation Base (model: R5-BS) InternalPower: Via the base (model: R5-BS) Isolation: T-Link to internal bus or internal power RUN indicator: Bi-color (green/red) LED; green in normal communications; red when receiving (Function selected with DIP SW3) ERR indicator: Bi-color (green/red) LED; the green ON/blinks in communication errors; red when transmitting (Function selected with DIP SW3) Data allocation: Mode 1 or 2 set with the side DIP switch DIP SW other functions · I/O points · Input or output or I/O mixed Refer to the instruction manual for details.
INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R5-BS) Weight: 150 g (0.33 lb)
PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 500 V AC @ 1 minute (T-Link to internal bus or internal power)
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
I/O DATA DESCRIPTIONS The data allocations for typical I/O modules are shown below. Refer to the manual for each module for detailed data allocations.